| Product Model |
AP‑400 |
| Rated Capacity |
400 kVA |
| Input |
|
| Input Voltage |
3‑phase 3‑wire (Line‑to‑line voltage 380 V ±10%) + PE conductor |
| Input Frequency |
50 Hz ±5 Hz |
| Output |
|
| Rated Output Voltage |
3‑phase 4‑wire (Line‑to‑line voltage 440 V), customizable upon request |
| Steady‑state Load Voltage Regulation |
≤1.5% |
| Rated Output Frequency |
50 Hz / 60 Hz |
| Output Frequency Stability |
≤±0.1% |
| Output Voltage Phase |
120° ±2° |
| Output Voltage Waveform Distortion |
Sine wave ≤3% (at rated voltage, resistive load) |
| System Efficiency |
≥90% (at rated load) |
| Overload Capacity |
100%‑105%: continuous operation
105%‑125%: 10 minutes
125%‑150%: 1 minute
150%‑200%: 5 seconds
>200%: immediate protection
|
| Control & Display |
|
| Control Method |
IGBT / SPWM pulse‑width modulation |
| Operation Mode |
Touch‑screen operation |
| Display Method |
Input side: electrical parameter meter;
Alarm messages & internal parameters: displayed via touch screen;
Output side: multi‑function electrical parameter meter
|
| Touch‑screen Display Resolution |
4‑digit voltage display, resolution: 0.1 V
4‑digit frequency display, resolution: 0.1 Hz
4‑digit current display, resolution: 0.1 A
4‑digit power display, resolution: 0.001 kW
|
| Protection |
|
| Protection Functions |
Output over‑/under‑voltage, over‑current, over‑temperature and short‑circuit protection |
| Ingress Protection Rating |
IP54 (container‑type unit); IP20 (indoor unit) |
| Environmental Conditions |
|
| Ambient Temperature |
‑10 ℃ ~ +40 ℃ |
| Relative Humidity |
≤95%RH (no condensation) |
| Altitude |
≤1000 m |
| Power‑frequency Withstand Voltage |
AC 2000 V / 1 min (input / output to enclosure) |
| Cooling Method |
Air‑conditioner and forced fan air cooling |
| Insulation Class |
Class F |
| Hot‑state Insulation Resistance |
>2 MΩ |
| Noise Level |
≤80 dB |